電力纜和控制纜基本要求:
FIRE PERFORMANCE IEC
60332-1-2
IEC 60332-3-22
HALOGEN-FREE IEC 60754 series
SMOKE EMISSION IEC 61034 series
OIL RESISTANCE IEC 60811-404
conditions
(SHF2 only) acc.
to 60092-360/SHF2
MIN. INSTALLATION
TEMPERATURE -15 °C
OPERATING
TEMPERATURE -40 – 80 °C fixed installation
MAX. CONDUCTOR
TEMPERATURE 90 °C
|
網(wǎng)絡(luò)線基本要求:
MAIN CHARACTERISTICS:
FIRE PERFORMANCE Dca-s1a, d1, a1
IEC 60332-1-2
IEC 60332-3-22
UV RESISTANCE
(Black or grey cables only) UL1581 section 1200
MAX. CONDUCTOR DC
RESISTANCE 93.8 Ω/km @20 °C
CONDUCTOR LOOP
RESISTANCE max. 19 Ω/100 m @20 °C
NOM. MUTUAL
CAPACITANCE ≤ 5.6 nF/100 m @1 kHz
CAPACITANCE UNBALANCE
PA24IR TO GROUND ≤ 1600 pF/km @1 kHz
MIN. INSULATION
RESISTANCE 5000 MΩ/m
IMPEDANCE 100 ± 25 Ω @100 MHz
RATED TEMPERATURE 75 °C
OPERATING
TEMPERATURE RANGE -20 °C - 75 °C
|